Skip to content

Troubleshooting

In the event of a fault, the power supply must be switched off first. Work on the electrical system must be carried out by qualified personnel only.

Typical faults, causes and checks

Symptom Possible cause Check / measure
A fused output does not work - associated fuse defective
- load defective
- cable interrupted or not connected correctly
- terminal not tightened sufficiently
- check the fuse and replace it if necessary
- check the load separately
- check the wiring of the affected fused output
- check the terminal connections for firm seating
An LED lights up - associated fuse defective - switch off the power supply
- check the fuse
- determine the cause of the tripping before inserting a new fuse
A fuse trips repeatedly - overload of the affected fused output
- short circuit in the wiring
- fault in the connected load
- unsuitable or incorrectly dimensioned fuse
- check the current consumption of the load
- check the cable routing and wiring
- check the load for defects
- compare the fuse rating with the technical requirements
Voltage at the fused output although no fuse is inserted - measurement voltage inherent to the LED indicator - not a malfunction
- no action required

Taking the device out of service in case of unexplained faults

If the cause of a fault cannot be clearly identified, the device must be taken out of service and inspected by qualified personnel. Operation with unexplained faults is not permitted.